4 Analog I/O Specifications

4.4.2 Analog Output Module I/O Allocation Screen

4.4.2
1) The I/O Traffic Cop (i.e., I/O Allocation) Screen
a) Mode Set
Select the data format input from the Analog Input Module.
For some Analog Input Modules, no selection of data format is required.
b) Service Scan (Normal/High-speed)
Set either Normal or High-speed scan for I/O data refresh cycle.
c) Soft Filter
Select one of the following types of software filter.
• NO FILTER
• AVE 3 TIMES
• AVE 5 TIMES

Analog Output Module I/O Allocation Screen

This section gives information on the MEMOSOFT I/O Traffic Cop Screen and the
Parameter Setting Screen.
Fig. 4.3 I/O Traffic Cop Screen
a) Module Type
Enter the Analog Output Module type, for example, 120AVO01000.
b) Set the I/O references to be used by the Analog Output Module.
When the first reference number is input, the cursor will move to the field for the last
reference number and the last reference number will be displayed automatically,
indicating the reference number that can be input. Press Enter Key to accept the
value, or change it to the desired value, if required.