4) The following diagram shows an example for terminal connections.
For Current Signal Source
External device
EXAMPLE
External device
For Voltage Signal Source
External device
External device
Note: (1) Isolation between Input Channels
There is no insolation provided between the input circuit channels. If isolation
between channels is required, use a commercial isolation amplifier for each
channel.
(2) Recommended Cables
Use shielded twisted-pair wire 1.3 mm
nect to the terminal block.
Shielded twisted-pair wire
+
A
-
4 to 20 mA
Shielded twisted-pair wire
+
A
-
4 to 20 mA
Shielded twisted-pair wire
+
V
-
1 to 5 V
Shielded twisted-pair wire
+
V
-
1 to 5 V
Grounding resistance
100 Ω max.
2
(AWG16) to 0.5 mm
4-17
4.1 Analog Input Specifications
1
CH1 S
2
CH1 +
3
Shield 1
4
CH1 -
CH2 S
5
CH2 +
6
Shield 2
7
CH2 -
8
CH3 S
9
CH3 +
10
Shield 3
11
CH3 -
12
13
CH4 S
14
CH4 +
15
Shield 4
16
CH4 -
17
Not connected
18
Not connected
19
FG
20
Not connected