6 Installation and Wiring
6.2.2 Wiring AC I/O Modules
2) AC Power Supply Cables
CAUTION
100-VAC 16-point Input Module
200-VAC 16-point Input Module
100/200-VAC 8-point Output Module
100/200-VAC 16-point Output Module
Relay Contact 16-point Output Module
Example 2: Load Driving Power Supply for 100/200 VAC 16-point Output Module
JAMSC-120DAO84300
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Common 1-1
Common 1-2
Output 9
Output 10
Output 11
Output 12
Output 13
Output 14
Output 15
Output 16
Common 2-1
Common 2-2
Fig. 6.2 Load Driving Power Supply
Do not allow foreign matter such as cable chips in the Modules or Mounting Bases.
Foreign matter in the Modules or Mounting Bases may cause fire, failures and/
or malfunctions.
a) Five types of AC I/O Modules are available. See Table 6.4.
To connect these I/O Modules to an AC power supply, use recommended size of
cable listed in Table 6.4. The cables differ in their allowable current capacity
depending on the conditions of use, such as the ambient operating temperature, so
check the conditions of use and select a cable of appropriate size.
Table 6.4 Power Supply Cable Size
Name
b) M3 Phillips screws are used in the external connection terminals. Use crimp termi-
nals that are specially designed for M3 Phillips screws for the Module end of the
power supply cable.
Fuse
Load
Fuse
Load
Load driving power
supply(single-phase,
100/200 VAC, 50/60 Hz)
Model No.
JAMSC-120DAI54300
JAMSC-120DAI74300
JAMSC-120DAO83000
JAMSC-120DAO84300
JAMSC-120DRA84300
6-16
Power Supply Cable Size
2
0.5 mm
(AWG20) to 1.3 mm
(AWG16)
2
1.3 mm
(AWG16) or larger
AC loads:
2
1.3 mm
(AWG16) or larger
2

Advertisement