Item
Maximum Heating Value
Hot Swapping
(Removal/insertion under power)
Approximate Mass
External Dimensions
Recommended Cable
* Overrange is detected when +10.24 V < Channel input signal or
Channel input signal < -10.24 V
2) Input Characteristics
The following diagram show the input characteristics. Two modes are available:
±2000 mode and 0-4000 mode. The mode is selected by I/O allocation.
Analog input value
≤-10.24 V
-10.00 V
-5.00 V
0.00 V
+5.00 V
+10.00 V
≥+10.24 V
Input register value
Note: (1) For ±2000 mode, if input register value exceeds the range
from -10.24 V to +10.24 V, the analog input value will be
clamped at -2048 or +2048.
(2) For 0-4000 mode, if input register value exceeds the range
from -10.00 V to +10.24 V, the analog input value will be
clamped at 0 or 4048.
Specification
2.3 W
Permitted
300g
40.3×130×103.9 mm (W×H×D)
Shielded twisted-pair wires
2
1.3 mm
(AWG16) to 0.5 mm
Input register value
±2000 mode
-2048
-2000
-1000
0000
+1000
+2000
+2048
0-4000 mode
+2000 mode
Analog input value (V)
4-3
4.1 Analog Input Specifications
2
(AWG20)
0-4000 mode
0000
0000
1000
2000
3000
4000
4048