3 Digital I/O Specifications
3.4.3 64-point Input Modules
2) Module Type Setting
3) I/O Reference Number Setting
Type of Input
Input Relays
Input Registers
Refer to the following manuals for specific setting procedures.
• MEOCON GL120, GL130 MEMOSOFT for P120 Programming Panel User's
Manual (Manual No. SIEZ-C825-60.7), Chapter 7 Setting System Configuration.
• MEMOCON GL120, GL130 MEMOSOFT for DOS User's Manual (Manual No.
SIEZ-C825-60.10), Chapter 7 Setting System Configuration.
• MEMOCON GL120, GL130 MEMOSOFT for Windows User's Manual (Manual
No. SIEZ-C825-60.25), Chapter 6 Setting the Module Configuration.
The type of Input Module mounted in the slot is set as the Module type. Only the last
11 alphanumeric characters of the model number are necessary. For example
120DDI36400 is the Module type for the JAMSC-120DDI36400.
(a) The leading I/O reference number used by the Input Module is set.
(b) Any one of the I/O reference numbers and points listed in the following table
can be set.
References for I/O Allocation
CPU10, CPU20, CPU21
100001 to 101024
300001 to 300512
(c) When an input relay is set, the leading I/O reference number must satisfy the
following equation:
Leading reference number of I/O relay = 100001 + 16 n
where n = 0 to 63 for the CPU20 and
n = 0 to 255 for the CPU30
For example, 100001 can be set as the leading reference number, but
100002 cannot.
CPU30, CPU35
100001 to 104096
300001 to 300512
3-88
Points/Registers
64 points
4 registers