3 Digital I/O Specifications
3.4.6 32-point Output Modules
2) Module Type Setting
3) I/O Reference Number Setting
Type of Output
Output coils
Output registers
4) I/O Data Format
The type of Output Module mounted in the slot is set as the Module type. Only the
last 11 alphanumeric characters of the model number are necessary. For example
120DDO35410 is the Module type for the JAMSC-120DDO35410.
(a) The leading I/O reference number used by the Output Module is set.
(b) Any one of the I/O reference numbers and points listed in the following table
can be set.
CPU10, CPU20, CPU21
000001 to 001024
400001 to 400512
(c) When an output coil is set, the leading I/O reference number must satisfy the
following equation:
Leading reference number of I/O coil = 000001 + 16 n
where n = 0 to 63 for the CPU20 and
n = 0 to 255 for the CPU30
For example, 000001 can be set as the leading reference number, but
000002 cannot.
The following items can be set to define the I/O data format. There is, however, gen-
erally no need to change these settings because the default settings can be used
for most normal applications.
a) Bit Order
I/O can be processed by handling data either in ascending or descending order of
the bits. This is explained next for allocation of both output coils and output regis-
ters.
(1) When 32-point output coils are allocated from 000001, the bit order can be set
to either "MSB" or "LSB," as described in the following table and shown in the
illustration below it. Allocation is performed in units of 16 output points.
Output Coil MSB Setting
Output Coil LSB Setting
Refer to Fig. 3.11 Allocation of Output Coils for details.
References for I/O Allocation
CPU30, CPU35
000001 to 004096
400001 to 400512
The leading output reference number (000001) is allocated to the
smallest output number of the first 16 output points (output 1) on the
Output Module. The next output reference number (000017) is allo-
cated to the smallest output number of the second 16 output points
(output 17) on the Output Module.
The leading output reference number (000001) is allocated to the
largest output number of the first 16 output points (output 16) on the
Output Module. The next output reference number (000017) is allo-
cated to the largest output number of the second 16 output points
(output 32) on the Output Module.
3-98
Points/Registers
32 points
2 registers