Replacement Of Heat Exchange Unit And Fan - ABB IRC5 Product Manual

Robot controller
Hide thumbs Also See for IRC5:
Table of Contents

Advertisement

4 Repair activities, controller IRC5

4.7. Replacement of heat exchange unit and fan

4.7. Replacement of heat exchange unit and fan
Location
The heat exchanger unit is located in the back of the Control Module as shown below. On the
Dual Cabinet Controller the heat exchange unit is located on the Control Module.
xx0500001952
A
B
C
D
Required equipment
Fan with receptacle
Fan with receptacle
Heat exchange unit
Adhesive
Standard toolkit
Other tools and procedures may
be required. See references to
these procedures in the step-by-
step instructions below.
Circuit Diagram
196
Fan
Heat exchanger
Top cover
Attachment screws (4 pcs)
Equipment
Spare part no.
Note
3HAC021700-001
Room temp MAX52°C
IRB 6600, IRB 7600 IRB 660 and
IRB 6620
3HAC021702-001
Room temp (MAX45°C) or Room
temp (MAX52°C)
IRB 140, IRB 340 IRB 1400,
IRB 2400, IRB 4400 and
IRB 1600
3HAC024439-001
Room temp MAX52°C
Product name, Casco S55
The contents are defined in
section
page
These procedures include
references to the tools required.
See
Standard toolkit, IRC5 on
299.
Circuit Diagram on page
Continues on next page
3HAC021313-001 Revision: P
319.