9.3

Wiring inside and outside the panel

Wiring inside

Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other.
Noise interference that is generated by cables that cross each other may cause malfunctions.
Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers (NFB),
electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors.
Refer to the section to follow for surge killers.
Page 226 Installing the Battery
Uncrossed power lines and
communication cables
Power
cable
PLC
NFB
MC
MC
Drive control wire
Terminal block

Outside the panel

To pull the power line and communication cable out of the panel, make two pullout holes away from each other and pull the
cables through.
Putting both cables through the same pullout hole will increase noise interference.
Connection
cable
Pullout hole
Keep the power line and communication cable inside the duct at least 100 mm away from each other.
If that is not possible, the use of a metal separator inside the duct can reduce noise interference.
100(3.94) or more
GOT connection cable
PLC I/O wire
RA
RA
Power line
Power line
Pullout hole
Wiring duct
Power line
Signal line
Power line
Crossing power lines and
communication cables
Power
cable
PLC
NFB
PLC
I/O wire
MC
MC
Drive control wire
Terminal block
Connection
cable
Separator
Signal line
Unit: mm (inch)
9 HANDY GOT POWER WIRING AND SWITCH HANDLING
9.3 Wiring inside and outside the panel
GOT connection cable
RA
RA
9
337