The following tables list the distance required between the GOT and the other devices.
The dimensions within the parentheses apply when no equipment generating radiated noise (such as a contactor) or heat is
installed near the GOT.
However, always keep the ambient temperature of the GOT to 55 °C or lower.
Unit: mm (inch)
Item
A
GOT only
Ethernet communication unit fitted
Bus connection unit is fitted
Serial connection unit is fitted
CC-Link communication unit (GT15-J61BT13) fitted
MELSECNET/H communication unit (coaxial) fitted
MELSECNET/H communication unit(optical) fitted
CC-Link IE TSN communication unit fitted
CC-Link IE Controller Network communication unit fitted
CC-Link IE Field Network communication unit fitted
Printer unit fitted
External I/O unit fitted
Sound output unit fitted
B
C
When the SD card is used
When the SD card is not used
D
*3
E
*1 This value is for use of the coaxial cable 3C-2V (JIS C 3501).
For specifications of the cable, refer to the GOT2000 Series Connection Manual for a controller used.
*2 This value differs depending on the cable used.
*3 When opening or closing the battery cover: 72(2.83) or more.
GT25
GT2512-S
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
*1
48(1.89) or more
[38(1.50) or more]
*2
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
48(1.89) or more
[18(0.71) or more]
Horizontal: 78(3.07) or more [18(0.71) or more]
Vertical: 48(1.89) or more [18(0.71) or more]
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
[20(0.79) or more]
Horizontal: 50(1.97) or more [20(0.79) or more]
Vertical: 80(3.15) or more [20(0.79) or more]
100(3.94) or more
[20(0.79) or more]
GT2510-V
GT2508-V
48(1.89) or more
[29(1.14) or more]
23(0.91) or more
[29(1.14) or more]
48(1.89) or more
67(2.64) or more
[45(1.77) or more]
50(1.97) or more
6 INSTALLATION AND REMOVAL
6.4 Installation Position
6
185