Mitsubishi Electric GOT2000 Series Hardware User Manual page 275

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

3.
Fit the connector conversion box into the installation hole from the back side of the control panel, and fix the box with four
M4 screws (user prepared).
In the connector conversion box, thread of M4, 6 mm in depth is cut in each mounting hole.
Prepare four M4 mounting screws separately while considering the thickness of the panel face.
Tighten the screws within the specified torque range (0.69 N•m to 0.88 N•m).
Overtightening the screws may cause damage.
Make sure that interfering objects are not located within 65 mm from the rear face so that the connector of a PLC cable is not
hindered.
Also, make sure that interfering objects are not located within 25 mm from the upper side so that the
terminal block is not hindered.
Make sure that interfering objects are not located within 50 mm from the lower side so that the Ethernet
port and terminal block are not hindered.
Other device
ON
OFF
65 (2.56)
Other device
7 OPTION AND COMMUNICATION CABLE FOR HANDY GOT
25 (0.99)
ES1A
ES1B
ES2A ES2B ES3A ES3B
FG
ES1A
ES1B
ES2A ES2B ES3A ES3B
-INPUT 24VDC+
ID No.
U
L
RS-232
RS-422
10BASE-T
SW-COM
SW2
SW4
SW6
KSW1 DSW1 DSW2
100BASE-TX
SW1
SW3
SW5
KSW-COM
KSW2
DSW1 DSW2
25 (0.99)
Unit: mm (inch)
7.1 Connector Conversion Box
7
273