Create the cables (RS-232 cable, RS-422/485 cable) for connecting the GOT and a controller by yourself.
For how to create a cable, refer to the following.
GOT2000 Series Connection Manual For GT Works3 Version1 compatible for a controller used
Treatment of the RS-232 cable and RS-422/485 cable
When the GOT is connected to a controller, configure the system according to the EMC Directive
specifications for the controller.
The following shows the recommended instructions to comply with the EMC Directive.
However, the manufacturer of the equipment must determine the method to comply with the EMC Directive
and conformance to the directive.
• RS-422/485 cable
When connecting each signal wire (except SG and FG wires), twist two signal wires as shown below.
SDA
SDB
RDA
RDB
Connect two or more SG wires.
• RS-232 cable
Twist each signal wire (except SG and FG wires) with the SG wire.
RD
SD
DTR
DSR
SG
Install a ferrite core to the cable in the positions as shown in the figure below.
GOT side
100 or less
(3.94)
Ferrite core
(ZCAT3035-1330)
5 EMC DIRECTIVE AND LOW VOLTAGE DIRECTIVE
RDA
RDB
SDA
SDB
SD
RD
DSR
DTR
SG
PLC CPU side
100 or less
Unit: mm (inch)
(3.94)
5.2 EMC Directive Requirements
5
163