Mitsubishi Electric GOT2000 Series Hardware User Manual page 375

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

Installation status
■Current status
Check if the FG cables of the control equipment (such as a PLC) and the power equipment (such as a servo amplifier) are
connected as shown in "a" of the following figure.
PLC
Servo amplifier
Connection cable
CN1A
CN1B
FG
LG
CN2
CN3
FG
a
Panel grounding
■Measure when a single ground cable is led
Perform independent grounding at two places as shown in Figure A.
The independent grounding reduces the influence of noise.
When independent grounding is unavailable, perform shared grounding as shown in Figure B.
Figure A
PLC
Servo amplifier
Connection cable
CN1A
CN1B
FG
LG
CN2
CN3
FG
Terminal
Panel grounding
block
Grounding for
control system
Grounding for power system
Check result
□ Applicable
□ Not applicable
FG
GOT
LG
Panel grounding
Figure B
Servo amplifier
CN1A
CN1B
CN2
CN3
GOT
FG
FG
LG
Terminal block
Panel grounding
Grounding for power system
PLC
Connection cable
FG
LG
FG
Panel grounding
LG
Panel grounding
12.1 GOT Restoration Sheets
Effect
□ Effective
□ Ineffective
GOT
12 TROUBLESHOOTING
373