11.2

Periodic Inspection

Half-yearly or yearly inspection items
Inspect the following items when moving or modifying equipment, or changing wiring.
Item
Inspection item
1
Surrounding
Ambient temperature
environment
Ambient humidity
Atmosphere
2
GOT with 100 V
Power supply
AC - 240 V AC
voltage check
power
GOT with 24 V
Input polarity of 24 V
DC power
DC power
3
Installation status
Looseness
Foreign material
adherence
4
Connection status
Loose terminal
screws
Proximity of
solderless terminals
Loose contactors
5
Battery
*1 The criterion varies with the installation orientation.
For the details, refer to the following.
Page 194 Control Panel Inside Temperature and GOT Installation Angle
Inspection method
Measure corrosive gas with a
thermometer or hygrometer.
Measure voltage across the 100 V
AC terminal to the 240 V AC
terminal.
Measure voltage across 24 V DC
terminals.
Move the unit.
Visual check
Retighten screws with a screwdriver.
Visual check
Visual check
Check the voltage status of the GOT
built-in battery in [Time] of the utility.
GOT2000 Series User's Manual
(Utility)
Criterion
Corrective action
Display section
0 °C to 40 °C
For use in a control panel, the
control panel inside
*1
Other sections
temperature is the ambient
10 % RH to 90% RH
temperature.
No corrosive gas
85 V AC to 242 V AC
Change the power supply.
Connected according to terminal
Change wiring.
markings on the GOT power
supply section
Mounted firmly
Retighten screws.
No foreign matter adherence
Remove the foreign material
and clean.
Not loose
Retighten terminal screws.
Proper intervals
Correct intervals.
Not loose
Retighten contactor fixing
screws.
No alarm
Replace the battery with a
new battery when the current
battery has reached the
specified life span, even if the
low voltage is not indicated.