GT25-S, GT25-V
Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
GT2512-S, GT2510-V, GT2508-V, GT2505-V
■Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be
within 40 °C.
GOT
Display
section
Control panel
or others
■Installing the GOT vertically
When the GOT is installed at a 90-degree angle, the control panel inside temperature must be within 55°C
When the GOT is installed at any angle other than 90°, the control panel inside temperature must be within 40°C.
GOT
Display
section
Control panel
or others
*1 For GT2505-V, the control panel inside temperature must be within 50°C.
105°
60°
90°
6.5 Control Panel Inside Temperature and GOT Installation Angle
*1
.
6 INSTALLATION AND REMOVAL
6
197