GT23
GT23
Regardless of the installation orientation, install the GT23 so that the following conditions are satisfied.
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.When
the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be within 40
°C.
GOT
Display
section
Control panel
or others
GT21
Install the GOT with its display section positioned as shown below.
Using the GOT with the installation angle other than the following accelerates the deterioration of the GOT.
GT21
■Installing the GOT horizontally
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 55 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be
within 40 °C.
GOT
Display
section
Control panel
or others
■Installing the GOT vertically
When the GOT is installed at any angle from 60 ° to 105 °, the control panel inside temperature must be within 50 °C.
When the GOT is installed at any angle outside the range from 60 ° to 105 °, the control panel inside temperature must be
within 40 °C.
GOT
Display
section
Control panel
or others
105°
60°
105°
60°
105°
60°
6.5 Control Panel Inside Temperature and GOT Installation Angle
6 INSTALLATION AND REMOVAL
6
199