Commissioning And Starting Up The Rtu - Siemens SIMATIC RTU3030C Operating Instructions Manual

Telecontrol - rtu
Hide thumbs Also See for SIMATIC RTU3030C:
Table of Contents

Advertisement

Connecting up, installation, commissioning

3.8 Commissioning and starting up the RTU

Connecting the external power supply to X10 IN
Finally connect the external power supply (voltage input) of the RTU to terminal block
X10 IN.
Only connect safety extra-low voltages (SELV), refer to the section Interfaces and
connectors (Page 43).
● X10 IN
– L+ Voltage input 18.8 ... 28.8 VDC
– M
Note the maximum power consumption in the section Technical data (Page 261).
3.8
Commissioning and starting up the RTU
Note
Startup with an SD card that is not brand new
If the RTU starts up with an SD card that is not brand new, observe the behavior of the RTU
in terms of the configuration file used, refer to the section Configuration (Page 99).
Requirements for commissioning
Prior to commissioning the RTU, make sure that the following conditions are met:
● The system is completely installed:
RTU, if applicable battery modules, protective housing, relevant sensors/actuators, if
applicable antenna, if applicable external power supply
● The RTU and the sensors/actuators belonging to it are completely wired.
● The communications partner - if configured - is reachable.
● The configuration data is loaded on the RTU.
Note
Copying the configuration data to other RTUs
If you install a lot of RTUs which use a lot of identical configuration data, you can transfer
the configuration data of one RTU to the other RTUs using the configuration file. For
information on this refer to the WBM > "Maintenance".
● When mobile wireless communication is intended: The SIM card is plugged in.
66
Functional ground
Do not use the functional ground for grounding the RTU. For grounding the system,
refer to the section Grounding and overvoltage protection (Page 60).
Reference potential
Operating Instructions, 09/2017, C79000-G8976-C382-04