Current impulse relay

Function
The input parameters "Set" and "Reset" set the output to 1 or 0:
● Set
A positive edge (0 → 1) sets the output to 1.
● Reset
A positive edge (0 → 1) sets the output to 0.
As with the latching relay (see above) the parameters "Set" and "Reset" both have a latching
function.
When "Set" and "Reset" have the same value (both = 0 or both = 1) the switching of the
output is controlled by the function parameter "RS/SR priority":
● SR: The output is set to 1.
● RS: The output is set to 0.
The "Trigger" input causes a status change at the output regardless of its previous status.
● Output = 0: A positive edge at the "Trigger" input sets the output to 1.
● Output = 1: A positive edge at the "Trigger" input sets the output to 0.
The "Trigger" input has the function of a button. A tag can be connected to its input that
generates short pulses (current impulses).
Diagram
The following diagram shows an example of the effect on the output.
The blue arrow indicates a value change of the output Q that is caused by the programming
of the RS/SR priority.
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Tag type / range of
Description
values
SR
RS
Digital output / bit
Tag for the output.
memory
5.10 Switch and relay blocks
SR
If "Set" and "Reset" have the same value, "SR" caus-
es the output to be set to 1.
RS
If "Set" and "Reset" have the same value, "RS" caus-
es the output to be set to 0.