Connecting up, installation, commissioning

3.2 Requirements for commissioning

DIN rail
In the ATEX and IECEx area of application only the Siemens DIN rail 6ES5 710-8MA11
may be used to mount the RTU and the battery modules.
3.1.3

Notices regarding use in hazardous areas according to UL HazLoc

EXPLOSION HAZARD
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-
hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations
only.
3.2
Requirements for commissioning
Prior to commissioning
The following requirements must be met before you commission the RTU:
● Configuring the RTU
For the communication of the RTU with a configuration computer via the LAN interface,
you need to set the interface of the configuration computer according to the subnet
parameters of the RTU, refer to section LAN (Page 107). As an alternative, you can
activate the DHCP functionality of the RTU on the WBM page "LAN".
With the factory setting the RTU is set to manual IP address assignment with IP
192.168.0.3.
● Formatted SD card (optional)
If you want to use an SD card, make sure that the card is correctly formatted, see also
the section SD card / using and formatting SMC (Page 55).
54
WARNING
WARNING
Operating Instructions, 09/2017, C79000-G8976-C382-04