Advertisement

Programming
5.9 Blocks for messages
5.9.2

Send e-mail

Function
When a configurable event occurs, transfers an e-mail message for sending.
Parameters
Parameters
Input parameters
En
Trigger
Send Immediately True / False
Function parameters
Recipient
Text
Attachment
Anhang gezippt
Output parameters
Done
242
Tag type / range of
Description
values
Enable parameter, see section Often used parameters
(Page 198).
True / False
Event that triggers the creation of the message.
Digital input / output /
bit memory
STATUS_ERROR
When there is an edge change 0 → 1 the message is
transferred for sending.
Digital input / output /
bit memory
With the setting "True", the message is always trans-
ferred immediately for sending.
STATUS_ERROR
With the setting "Not used" or "False", the message is
transferred for sending when the RTU establishes the
next connection to the partner.
The input parameter must be reset to 0 by the program.
"Recipient group"
Selection of the user groups configured in "Users /
groups"
"Texts"
Selection of a message text configured in "Tags" >
"Texts"
You have the option of attaching a file stored on the RTU
No attachment
to the e-mail.
Entire diagnostics
buffer
Current log file
Current process
image
ON / OFF
Adds the file to the attachment as a compressed zip
archive.
Digital output / bit
Status display:
memory
0: Message could not be transferred to the transfer
buffer. The buffer is possibly full.
1: Message could be transferred successfully to the
transfer buffer.
Operating Instructions, 09/2017, C79000-G8976-C382-04