Note
You must not install the device on a wall in hazardous areas.
EXPLOSION HAZARD
The equipment is intended to be installed within an enclosure/control cabinet. The inner
service temperature of the enclosure/control cabinet corresponds to the ambient
temperature of the module. Use cables with a maximum permitted operating temperature of
at least 20 °C higher than the maximum ambient temperature.
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
3.1.2

Notices on use in hazardous areas according to ATEX / IECEx

To comply with EC Directive 2014/34/EU (ATEX 114) or the conditions of IECEx, this
enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN
60529.
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient in excess of 50 °C, only use cables with admitted maximum operating temperature
of at least 80 °C.
Take measures to prevent transient voltage surges of more than 40% of the rated voltage.
This is the case if you only operate devices with SELV (safety extra-low voltage).
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
WARNING
WARNING
WARNING
WARNING
WARNING
Connecting up, installation, commissioning
3.1 Important notes on using the device