5.6

Blocks for time functions

Note
Higher energy consumption due to additional update cycles
Time functions can generate additional update cycles to update the outputs of the function.
Additional update cycles can significantly increase power consumption.
5.6.1

On delay

Function
When there is an edge change 0 → 1 at the "Trigger" input, the configurable time of the On
delay is started. After the On delay has elapsed, the output is set to 1.
If "Trigger" changes back to 0 before the On delay has elapsed, the On delay is stopped and
the output remains set to 0.
If "Trigger" is reset to 0 before the On delay (Q = 1) has elapsed, the output (Q) is reset to 0.
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Tag type / range of
Description
values
Analog memory bit
Tag in which the calculated quotient is output.
Configured as a
floating-point
number:
3.402823 e-38 ..
3.402823 e+38
Configured as a
counter:
0 .. 4294967295
Digital output / bit
Error display:
memory
5.6 Blocks for time functions
0: Block processing completed without errors
1: Block processing aborted with an error
For the meaning, see Often used parameters
(Page 198).
Programming
207