Advertisement

Programming
5.6 Blocks for time functions
Parameters
Parameters
Input parameters
En
Trigger
Reset
Function parameters
On delay (ms)
On delay max.
(ms)
Off delay min
(ms)
Off delay max.
(ms)
Output parameters
Output
5.6.7

Year timer

Requirement
Requirement for a precise calculation is the time-of-day synchronization of the RTU.
Function
Year timer
For the year timer a time per calendar year and/or per month can be specified in the function
parameters during which the output is set to 1.
214
Range of values
Description
Enable parameter, see section Often used parameters
(Page 198).
When there is an edge change 0 → 1 the On delay is
True / False
started.
Digital input /
When there is an edge change 1 → 0 the Off delay is
output / bit
started.
memory
With the setting "True" the trigger is always active.
STATUS_ERROR
With the setting "False" the block is never processed.
When there is an edge change 0 → 1 On delay is
True / False
stopped and the output is set to 0. As long as the input is
Digital input /
set to 0, the value of "Trigger" is ignored.
output / bit
When there is an edge change 1 → 0 the block can be
memory
processed again.
STATUS_ERROR
With the setting "True" an edge change 0 → 1 at "Trigger"
is permanently ignored. The "Off delay " function is there-
fore also turned off.
With the setting "False" the input is never active.
100 .. 999999999
Minimum time in the clock cycle during which the output
= 1.
100 .. 999999999
Maximum time in the clock cycle during which the output
= 1.
100 .. 999999999
Minimum time in the clock cycle during which the output
= 0.
100 .. 999999999
Maximum time in the clock cycle during which the output
= 0.
Tag in which the pulses generated by the block are out-
Digital output / bit
put.
memory
Operating Instructions, 09/2017, C79000-G8976-C382-04
RTU3030C