COMMISSIONING THE BURNER

The LMV2x complete programming must be performed on units that has never been set before or reset units (e.g. spare parts).
The programming procedure is performed by setting the following main parameters:
1
if LMV.. is a spare part, insert burner ID (parameter 113) at least 4 digit.
2
type of fuel train (parameter "201")
3
air/fuel ratio curvepoints (Block "400")
4
maximum load percentage (parameter "546")
5
minimum load percentage (parameter "545")
CAUTION: if an error message as "Loc.." appears when the unit is turned to on for the first time, press ENTER (InFo) until
the "Reset" message apperas. After few seconds, the message "OffUpr" will be displayed.
This message shows that the unit has not been programmed before or that the operating mode (fuel train) is not set yet or that the unit
has not been completely programmed. Pree keys F (Fuel) and A (Air)
will show 7 bars the first on the left is flashing. If the display shows "Off", it means that the unitis already set, then see the instructions on
chapter "Adjsuting the burner with LMV2x already programmed").
At the first LMV startup, the AZL display will show
It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert.
Push F (fuel) and A (Air) together untilthe display shows code and then a 7 digit dashed line blinking on the left.
Press the "+" key until the first character of the password (the default password is 9876), then press ENTER (InFo), the character now
turn to a bar while the second bar starts flashing. Press "+" until the second character is entered, then press ENTER (InFo).
Repeat the procedure until the last character si set, then press ENTER (InFo), then ENTER again until the message PArA appears:
then the first parameters block ("400") will be shown:
Press ENTER (InFo) again, to gain access to programming the operating mode (fuel train):
In the example, set configuration 1 = direct gas ignition (G mod).
Other possibilities are below listed:
at the same time unitl the display shows code and next it