Siemens REP-1 Installation Instructions Manual

Network repeater module

Advertisement

Quick Links

Installation Instructions
Model REP-1
Network Repeater Module
INTRODUCTION
The Model REP-1 from Siemens Industry,
Inc., is an MXL module that permits the
user to extend the distance of the MXL
RS-485 network as well as the distance of
the NIM-1R RS-485 network. The REP-1
also supports both Style 4 and Style 7
wiring.
The MXL network uses an RS-485 inter-
face for its network wiring. The RS-485
supports up to 32 nodes on each pair of
wires (See Note below).
Note: A node is any location where
the network wires are con-
nected to the screw terminals
of an MXL System module.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-092686-8
The REP-1 module reproduces the RS-485
signal on a new pair of wires. The new
signal makes it possible to add more nodes
to the system.
OPERATION
An REP-1 Repeater module may be used to:
Figure 1
REP-1 Repeater PC Board
1. Add nodes to the end of a system
network by providing a repeated
network,
2. Add a Style 4 or Style 7 tap to a
system, or
3. Add a Style 4 tap to a Style 7
network.
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Advertisement

loading

Summary of Contents for Siemens REP-1

  • Page 1 OPERATION also supports both Style 4 and Style 7 wiring. An REP-1 Repeater module may be used to: The MXL network uses an RS-485 inter- 1. Add nodes to the end of a system face for its network wiring. The RS-485...
  • Page 2 MMB so as to protect ground fault isolation circuits When an REP-1 is used to add Style 4 to a Style 7 network, REP-1 connects to two For additional information on the MXL/MXLV nodes, thus adding 30 new nodes.
  • Page 3: Electrical Ratings

    ELECTRICAL RATINGS CAUTION For NIM-1R Network i t c If a REP-1 is used on a NIM-1R i t c network, place the JP1 jumper in the PSR position, no matter in which type of cabinet the REP-1 is installed.
  • Page 4: Installation

    AC. (To power to secure the card guide. up, first connect the AC and then the battery.) 4. Install the REP-1 by sliding it into Install the REP-1 in the MXL card cage the card guides and firmly seat- Model MOM-4 by inserting the REP-1 ing it in the card edge connector.
  • Page 5: Electrical Connections

    Basic Repeater (See Figures 3 and 4) The new repeated network begins at the REP-1 and also has an end of line resis- A basic repeater connects to the network tor. Figure 3 shows the connection for a at the end of the run. A repeater can ex- Style 4 network.
  • Page 6 4 tap on a Style 7 network. Figure 6 shows Locate the REP-1 between the two ends of a Style 4 tap that begins at the REP-1. This the primary network and do not use an tap can also be run in two directions if the...
  • Page 7 Notes: 1. Use 18 AWG minimum wire. 2. Limit maximum resistance per pair to 80 ohms. 3. Use shielded twisted pair. 4. Terminate the shield ONLY at the MMB enclosure. 5. The wiring is power limited according to NFPA 70 per NEC 760.
  • Page 8 Siemens Industry, Inc. Siemens Building Technologies, Ltd. Building Technologies Division Fire Safety & Security Products Florham Park, NJ 2 Kenview Boulevard Brampton, Ontario P/N 315-092686-8 L6T 5E4 Canada...