Siemens SIMATIC RTU3030C Operating Instructions Manual page 171

Telecontrol - rtu
Hide thumbs Also See for SIMATIC RTU3030C:
Table of Contents

Advertisement

● Station number
Number of the connection in TCSB
Range of values: 1 .. 8000
Range of values in TCSB: 1...8000 (throughout the entire TCSB system)
With connections between different RTUs and TCSB, the station number within a project
must be different for every RTU.
● Telecontrol password
Password for authentication of the RTU with TCSB. Is configured in TCSB for every
station.
Rules: 8 .. 29 characters from the ASCII character set 0x20.. 0x7E
● Allow HTTP/S access via TeleControl Basic
If the option is enabled this makes connection establishment possible from a PC to the
Web server of the RTU via HTTP/S and the TeleControl Basic tunnel. The connection
depends on the settings for HTTPS in "Security".
Transmission settings
A connection establishment for example via the mobile wireless network can take several
seconds. This depends on the particular network, on the current network load and on any
maintenance work of the network provider.
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Configuration (WBM)
4.20 Telecontrol
171