Siemens SIMATIC RTU3030C Operating Instructions Manual page 41

Telecontrol - rtu
Hide thumbs Also See for SIMATIC RTU3030C:
Table of Contents

Advertisement

"Meaning" column
If a cell in the "Meaning" column has several entries with bullets, all or only individual
meanings may apply.
RTU status LEDs
Table 2- 4
Name
DC IN
BAT
STATUS
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
RTU status LEDs
Color
flashing green
green
red
flashing red
LEDs, connectors, buttons, card slots
Meaning
External power OFF
External voltage ON, voltage value in the range 10.8 ... 28.8
V, but not configured
External voltage ON, voltage value in the range 10.8 ... 28.8 V
No power supply from battery modules
Power supply from battery module 1 (directly on the RTU)
Power supply from battery module 2 (to the left of battery
module 1)
No error and sleep mode or service mode or update mode
Start-up after power ON
Configuration data is changed.
Resetting to factory settings initiated
Communication mode
Fault in the power supply
Battery supply that is not configured.
Battery supply with the configuration of an external
power supply
Critical battery capacity
External power supply that is not configured.
Mobile wireless error
Connection error
Error accessing the SIM card
Incorrect PIN
Time-of-day synchronization failed
Error in Logging
SD card does not exist
Access error
For diagnostics, refer to the messages in the diagnostics
buffer.
No configuration
Duplicate IP address
No IP lease received from DHCP server (when the IP
address is obtained automatically)
Overload at one of the voltage outputs:
X10 CTRL / X11 CTRL / X40 / X42
2.2 LEDs
41