Technical specifications - RTU3030C
Configurable input types
Digital outputs (X30, X31)
Quantity
Type and material
Connection type
Level logical = 1 when:
Level logical = 0 when:
Maximum switching frequency
Limit permanent current
Max. switched current
Max. switching voltage
Max. switching capacity
Mechanical lifetime of the con-
tacts (typ.)
Electrical lifetime of the contacts
(typ.)
Analog inputs (X41, X43)
Quantity
Connection type
Configurable input signals (typ,
range)
Accuracy
Resolution
Input resistance
RTU3030C
Operating Instructions, 09/2017, C79000-G8976-C382-04
Binary input
•
–
Minimum pulse length for binary input: 2 ms
Minimum pulse length in sleep mode or with logging activated: 100 ms
–
Filter time: 40 μs
Counter input
•
–
Input clock frequency: 1 .. 5000 Hz
A debounced signal transmitter is necessary.
4
Relay, silver/nickel gold plated
2-wire technology
Contact closed
Contact open
1 Hz
300 mA
300 mA
60 VDC
•
30 VAC effective (42.2 V peak voltage with non-sine-shaped voltage)
•
18 W (at 60 VDC)
10
switching cycles
8
At 12 V / 10 mA:
•
At 6 V / 100 mA:
•
At 60 V / 300 mA:
•
4
2-/3-/4-wire technology (L+, M, X+, X-)
Current
•
Voltage
•
Temperature (Pt1000)
•
Current
•
Voltage
•
Temperature
•
12 bits (0 .. 4095)
580 kΩ (voltage measurement)
•
243 Ω (current measurement)
•
5 x 10
switching cycles
•
7
1 x 10
switching cycles
•
7
5 x 10
switching cycles
•
5
0/4 .. 20 mA
•
0 .. 5/10 V
•
-80 ... +140 °C / -112 .. +284 °F
•
+/- 1 %
•
+/- 1 %
•
+/- 1.8 %
•
Technical data
263