Voltage Ctrl - ABB ACSM1 Firmware Manual

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

168
Group

47 VOLTAGE CTRL

Settings for overvoltage and undervoltage control, and supply voltage.
47
Firmware block:
VOLTAGE CTRL
(47)
This block
• enables/disables overvoltage and
undervoltage control
• enables/disables automatic
identification of supply voltage
• provides a parameter for manual
definition of supply voltage
• shows the supply voltage value
used by the control program.
Block outputs located in other
parameter groups
47.01 OVERVOLTAGE CTRL
Enables the overvoltage control of the intermediate DC link. Fast braking of a high inertia load causes
the voltage to rise to the overvoltage control limit. To prevent the DC voltage from exceeding the limit,
the overvoltage controller automatically decreases the braking torque.
Note: If a braking chopper and resistor or a regenerative supply section are included in the drive, the
controller must be disabled.
(0) Disable
(1) Enable
47.02 UNDERVOLT CTRL
Enables the undervoltage control of the intermediate DC link. If the DC voltage drops due to input
power cut off, the undervoltage controller will automatically decrease the motor torque in order to keep
the voltage above the lower limit. By decreasing the motor torque, the inertia of the load will cause
regeneration back to the drive, keeping the DC link charged and preventing an undervoltage trip until
the motor coasts to stop. This will act as a power-loss ride-through functionality in systems with high
inertia, such as a centrifuge or a fan.
(0) Disable
(1) Enable
Parameters and firmware blocks
VOLTAGE CTRL
1.19 USED SUPPLY VOLT
FW block:
VOLTAGE CTRL
Overvoltage control disabled.
Overvoltage control enabled.
FW block:
VOLTAGE CTRL
Undervoltage control disabled.
Undervoltage control enabled.
(page 66)
(see above)
(see above)