180
Group

55 COMMUNICATION TOOL

Settings for an RS-485 network implemented using optional JPC-01 Network
communication adapters. The network enables the use of a single PC or control
panel to control multiple drives.
For more information, see the JPC-01 Network communication adapter User's
manual (3AUA0000072233).
55
55.01 MDB STATION ID
Defines the ID of the drive on the RS-485 network. Each drive must have a dedicated ID number.
1...247
55.02 MDB BAUD RATE
Sets the baud rate on the network.
Note: This parameter must be set to
(0) Auto
(1) 9600
(2) 19200
(3) 38400
(4) 57600
55.03 MDB PARITY
Defines the use of parity bits. The same setting must be used in all on-line stations.
0...3
Parameters and firmware blocks
FW block: None
ID number. For drives, use a number between 1 and 31. (DriveStudio
uses ID number 247.)
FW block: None
(0) Auto
if a control panel is used as the controlling device.
Baud rate is determined automatically. At start-up, and after a
communication break, the initial rate is 9600 baud.
9600 baud.
19200 baud.
38400 baud.
57600 baud.
FW block: None
Number of parity bits.
• 0 = 8 none 1
• 1 = 8 none 2
• 2 = 8 even 1
• 3 = 8 odd 1