ABB ACSM1 Firmware Manual page 110

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

110
16.11 USER IO SET LO
Together with parameter
16.09 USER SET SEL
parameter
Status of source
defined by par.
Bit pointer: Group, index and bit
16.12 USER IO SET HI
See parameter
Bit pointer: Group, index and bit
16.13 TIME SOURCE PRIO
Selects which real-time clock source is adopted by the drive as the master real-time clock. Some
selections specify multiple sources that are in order of priority.
(0) FB_D2D_MMI
(1) D2D_FB_MMI
(2) FB_D2D
(3) D2D_FB
(4) FB Only
(5) D2D Only
(6) MMI_FB_D2D
(7) MMI Only
(8) Internal
16.20 DRIVE BOOT
(0) No action
(1) Reboot drive
Parameters and firmware blocks
FW block: None
16.12 USER IO SET
is set to
(10) IO
16.12
select the user parameter set as follows:
Status of source
16.11
defined by par.
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
TRUE
FW block: None
16.11 USER IO SET
FW block: None
Fieldbus (highest priority); drive-to-drive link; man-machine interface
(control panel or PC).
Drive-to-drive link (highest priority); fieldbus; man-machine interface
(control panel or PC).
Fieldbus (highest priority); drive-to-drive link.
Drive-to-drive link (highest priority); fieldbus.
Fieldbus only.
Drive-to-drive link only.
Man-machine interface (control panel or PC) (highest priority);
fieldbus; drive-to-drive link.
Man-machine interface (control panel or PC) only.
No external sources are used as master real-time clock.
FW block: None
Reboot not requested.
Reboot the drive control unit.
HI, selects the user parameter set when parameter
mode. The status of the source defined by this parameter and
User parameter set
16.12
selected
Set 1
Set 2
Set 3
Set 4
LO.