ABB ACSM1 Firmware Manual page 160

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

160
(1) KTY JCU
(2) KTY 1st FEN
(3) KTY 2nd FEN
(4) PTC JCU
(5) PTC 1st FEN
(6) PTC 2nd FEN
*Note: If one FEN-xx module is used, parameter setting must be either
1st
FEN. The FEN-xx module can be in either Slot 1 or Slot 2.
45.03 MOT TEMP ALM LIM
Defines the alarm limit for the motor overtemperature protection (when par.
=
(1) Alarm
0...200 °C
45.04 MOT TEMP FLT LIM
Defines the fault limit for the motor overtemperature protection (when par.
(2)
Fault).
0...200 °C
45.05 AMBIENT TEMP
Defines the ambient temperature for the thermal protection mode.
-60...100 °C
Parameters and firmware blocks
The temperature is supervised using a KTY84 sensor connected to
drive thermistor input TH.
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
The temperature is supervised using a KTY84 sensor connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. Note: This selection
does not apply for FEN-01. *
The temperature is supervised using 1...3 PTC sensors connected to
drive thermistor input TH.
The temperature is supervised using 1...3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 1 is used for the temperature supervision. *
The temperature is supervised using 1...3 PTC sensors connected to
encoder interface module FEN-xx installed in drive Slot 1/2. If two
encoder interface modules are used, encoder module connected to
Slot 2 is used for the temperature supervision. *
FW block:
or
(2)
Fault).
Motor overtemperature alarm limit.
FW block:
Motor overtemperature fault limit.
FW block:
Ambient temperature.
MOT THERM PROT
(see above)
MOT THERM PROT
(see above)
MOT THERM PROT
(see above)
(2) KTY 1st FEN
or
(5) PTC
45.01 MOT TEMP PROT
45.01
MOT TEMP PROT =