47.03 SUPPLVOLTAUTO-ID
Enables the auto-identification of the supply voltage. See also section
page 44.
(0) Disable
(1) Enable
47.04 SUPPLY VOLTAGE
Defines the nominal supply voltage. Used if auto-identification of the supply voltage is not enabled by
parameter
47.03
0...1000 V
47.05 LOW VOLT MOD ENA
Enables/disables (or selects a signal source that enables/disables) Low voltage mode. 0 = Low
voltage mode disabled, 1 = Low voltage mode enabled. See section
Bit pointer: Group, index and bit
47.06 LOW VOLT DC MIN
Minimum DC voltage for Low voltage mode. See section
250...450 V
47.07 LOW VOLT DC MAX
Maximum DC voltage for Low voltage mode. See section
Note: The value of this parameter must be higher than
350...810 V
47.08 EXT PU SUPPLY
Enables/disables (or selects a signal source that enables/disables) external power unit supply, used
with low DC supply voltages such as a battery. 0 = External power unit supply disabled, 1 = External
power unit supply enabled. See section
Bit pointer: Group, index and bit
FW block:
Auto-identification of supply voltage disabled. The drive sets the
voltage control and trip limits using the value of parameter
SUPPLY
VOLTAGE.
Auto-identification of supply voltage enabled. The drive detects the
supply voltage level during intermediate circuit charging and sets the
voltage control and trip limits accordingly.
FW block:
SUPPLVOLTAUTO-ID.
Nominal supply voltage.
FW block: None
FW block: None
Minimum DC voltage for Low voltage mode.
FW block: None
Maximum DC voltage for Low voltage mode.
FW block: None
Low voltage mode
VOLTAGE CTRL
(see above)
VOLTAGE CTRL
(see above)
Low voltage mode
Low voltage mode
(47.06 LOW VOLT DC MIN
on page 45.
Parameters and firmware blocks
Voltage control and trip limits
47.04
Low voltage mode
on page 45.
on page 45.
on page 45.
+ 50 V).