ABB ACSM1 Firmware Manual page 234

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

234
Code
Alarm
(fieldbus code)
2022
ENCODER 1 FAILURE
(0x7301)
2023
ENCODER 2 FAILURE
(0x7381)
Fault tracing
Cause
Encoder 1 has been activated
by parameter but the encoder
interface (FEN-xx) cannot be
found.
Encoder 2 has been activated
by parameter but the encoder
interface (FEN-xx) cannot be
found.
EnDat or SSI encoder is used in
continuous mode as encoder 2.
[I.e.
90.02 ENCODER 2 SEL
(3) FEN-11 ABS
and
91.02 ABS ENC INTERF
EnDat
or
(4)
SSI)
and
91.30 ENDAT MODE
=
(1)
Continuous
(or
91.25 SSI
MODE
=
(1)
Continuous).]
What to do
Check parameter
setting corresponds to encoder interface 1
(FEN-xx) installed in drive Slot 1/2 (signal
9.20 OPTION SLOT 1
2).
Note: The new setting will only take effect
after parameter
used or after the JCU control unit is powered
up the next time.
Check parameter
setting corresponds to encoder interface 2
(FEN-xx) installed in drive Slot 1/2 (signal
9.20 OPTION SLOT 1
2).
Note: The new setting will only take effect
after parameter
used or after the JCU control unit is powered
up the next time.
If possible, use single position transfer
instead of continuous position transfer (i.e. if
encoder has incremental sin/cos signals):
=
- Change parameter
ENDAT MODE
=
(2)
Otherwise use EnDat/SSI encoder as
encoder 1:
- Change parameter
to value
(3) FEN-11 ABS
90.02 ENCODER 2 SEL
Note: The new setting will only take effect
after parameter
used or after the JCU control unit is powered
up the next time.
90.01 ENCODER 1 SEL
/
9.21 OPTION SLOT
90.10 ENC PAR REFRESH
90.02 ENCODER 2 SEL
/
9.21 OPTION SLOT
90.10 ENC PAR REFRESH
91.25 SSI MODE
/
91.30
to value
(0) Initial
pos..
90.01 ENCODER 1 SEL
and parameter
to value
(0)
None.
90.10 ENC PAR REFRESH
is
is
is