6.07
TORQ LIM STATUS
Torque controller limitation status word.
Bit
0
UNDERVOLTAGE
1
OVERVOLTAGE
2
MINIMUM TORQUE
3
MAXIMUM TORQUE
4
INTERNAL CURRENT
5
LOAD ANGLE
6
MOTOR PULLOUT
7
Reserved
8
THERMAL
9
I2MAX CURRENT
10
USER CURRENT
11...15 Reserved
* Only one of bits 0...3 can be on simultaneously. The bit typically indicates the limit that is
exceeded first.
** Only either 9 or 10 can be on simultaneously. The bit typically indicates the limit that is exceeded
first.
6.12
OP MODE ACK
Operation mode acknowledge: 0 = Stopped, 1 = Speed, 2 = Torque, 3 = Min, 4 = Max, 5 = Add, 10 =
Scalar, 11 = Forced magn (ie, DC Hold).
6.14
SUPERV STATUS
Supervision status word. See also parameter group
Bit
0
SUPERV FUNC1
STATUS
1
SUPERV FUNC2
STATUS
2
SUPERV FUNC3
STATUS
3...15
Reserved
FW block:
DRIVE LOGIC
Name
Val.
1
Intermediate circuit DC undervoltage *
1
Intermediate circuit DC overvoltage *
1
Torque reference minimum limit is active. The limit is
defined by parameter
1
Torque reference maximum limit is active. The limit is
defined by parameter
1
An inverter current limit is active. The limit is identified by
bits 8...11.
1
For permanent magnet motor only: Load angle limit is
active, ie, the motor cannot produce more torque.
1
For asynchronous motor only: Motor pull-out limit is active,
ie, the motor cannot produce more torque.
1
Bit 4 = 0: Input current is limited by main circuit thermal
limit. Bit 4 = 1: Output current is limited by main circuit
thermal limit.
1
Inverter output current limit is active. **
1
Maximum inverter output current limit is active. The limit is
defined by parameter
FW block:
REFERENCE CTRL
FW block:
SUPERVISION
Name
Val.
Supervision function 1 is active (below low limit or over high
1
limit)
Supervision function 2 is active (below low limit or over high
1
limit)
Supervision function 3 is active (below low limit or over high
1
limit)
(page 88)
Information
20.07 MINIMUM
20.06 MAXIMUM
20.05 MAXIMUM
(page 150)
(page 145)
33
(page 145).
Information
Parameters and firmware blocks
79
TORQUE. *
TORQUE. *
CURRENT. **