(3) AI2 min tune
(4) AI2 max tune
13.12 AI SUPERVISION
Selects how the drive reacts when analogue input signal limit is reached. The limit is selected by
parameter
(0) No
(1) Fault
(2) Spd ref Safe
(3) Last speed
13.13 AI SUPERVIS ACT
Selects the analogue input signal supervision limit.
Bit
0
1
2
3
Example: If parameter value is set to 0010 (bin), bit 1 AI1>max is selected.
0b0000...0b1111
Parameters and firmware blocks
Current analogue input AI2 signal value is set as minimum value for
AI2, parameter
automatically.
Current analogue input AI2 signal value is set as maximum value for
AI2, parameter
action
FW block: None
13.13 AI SUPERVIS
ACT.
No action taken.
The drive trips on fault AI SUPERVISION.
The drive generates alarm AI SUPERVISION and sets the speed to
the speed defined by parameter
The drive generates alarm AI SUPERVISION and freezes the speed
to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
FW block: None
Supervision selected by parameter
AI1<min
AI1 signal value falls below the value defined by equation:
par.
13.03 AI1 MIN
AI1>max
AI1 signal value exceeds the value defined by equation:
par.
13.02 AI1 MAX
AI2<min
AI2 signal value falls below the value defined by equation:
par.
13.08 AI2 MIN
AI2>max
AI2 signal value exceeds the value defined by equation:
par.
13.07 AI2 MAX
AI1/AI2 signal supervision selection.
13.08 AI2
MIN. The value reverts back to
13.07 AI2
MAX. The value reverts back to
automatically.
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
13.12
- 0.5 mA or V
+ 0.5 mA or V
- 0.5 mA or V
+ 0.5 mA or V
(0) No action
46.02 SPEED REF
SAFE.
AI SUPERVISION is activated if
(0) No