ABB ACSM1 Firmware Manual page 251

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

Code
Fault
(fieldbus code)
0306
LICENSING
(0x6100)
0307
DEFAULT FILE
(0x6100)
0308
APPL FILE PAR CONF
(0x6300)
0309
APPL LOADING
(0x6300)
Fault code extension: 8
Fault code extension: 10
Fault code extension: 35
Fault code extension: 38
Fault code extension: 39
Fault code extension:
Other
0310
USERSET LOAD
(0xFF69)
0311
USERSET SAVE
(0xFF69)
0312
UFF OVERSIZE
(0x6300)
Cause
Drive internal fault
Note: This fault cannot be
reset.
Drive internal fault
Note: This fault cannot be
reset.
Corrupted application file
Note: This fault cannot be
reset.
Application file incompatible or
corrupted.
Note: This fault cannot be
reset.
Template used in the application
incompatible with drive
firmware.
Parameters defined in the
application conflict with existing
drive parameters.
Application memory full.
Too many powerfail parameters
Memory unit full
Corrupted application file
Loading of user set is not
successfully completed
because:
- requested user set does not
exist
- user set is not compatible with
drive program
- drive has been switched off
during loading.
User set is not saved because
of memory corruption.
UFF file is too big.
What to do
Contact your local ABB representative.
Contact your local ABB representative.
Reload application.
If fault is still active, contact your local ABB
representative.
Check the fault logger for a fault code
extension. See appropriate actions for each
extension below.
Change the template of the application in
DriveSPC.
Check the application for conflicting
parameters.
Reduce the application size and reload the
application.
Reduce the powerfail parameters from the
application.
Reduce the application size and reload the
application.
Reload application.
If fault is still active, contact your local ABB
representative.
Reload.
Check the setting of parameter
UNIT
SUPPLY.
If the fault still occurs, contact your local ABB
representative.
Contact your local ABB representative.
251