16 System; Group 17 Panel Display; Group 16 System - ABB ACSM1 Firmware Manual

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

108
Group

16 SYSTEM

Local control and parameter access settings, restoration of default parameter
values, save of parameters into permanent memory.
16
16.01 LOCAL LOCK
Selects the source for disabling local control (Take/Release button on the PC tool, LOC/REM key of
the panel). 1 = Local control disabled. 0 = Local control enabled.
Bit pointer: Group, index and bit
16.02 PARAMETER LOCK
Selects the state of the parameter lock. The lock prevents parameter changing.
Note: This parameter can only be adjusted after the correct pass code has been entered at parameter
16.03 PASS
(0) Locked
(1) Open
(2) Not saved
16.03 PASS CODE
After entering 358 at this parameter, parameter
The value reverts back to 0 automatically.
16.04 PARAM RESTORE
Restores the original settings of the application, ie, parameter factory default values.
Note: This parameter cannot be changed while the drive is running.
(0) Done
(1) Restore defs
(2) Clear all
16.07 PARAM SAVE
Saves the valid parameter values to permanent memory.
See also section
(0) Done
(1) Save
Parameters and firmware blocks
FW block: None
WARNING! Before activating, ensure that the control panel is not needed for stopping the
drive!
FW block: None
CODE.
Locked. Parameter values cannot be changed from the control panel.
The lock is open. Parameter values can be changed.
The lock is open. Parameter values can be changed, but the changes
will not be stored at power switch off.
FW block: None
FW block: None
Restoration is completed.
All parameter values are restored to default values, except motor
data, motor ID run results, and fieldbus, drive-to-drive link and
encoder configuration data.
All parameter values are restored to default values, including motor
data, motor ID run results and fieldbus and encoder configuration
data. PC tool communication is interrupted during the restoration.
Drive CPU is re-booted after the restoration is completed.
FW block: None
Programming via parameters
Save completed.
Save in progress.
16.02 PARAMETER LOCK
on page 30.
can be adjusted.

Advertisement

Table of Contents
loading