FIO_11_AI_slot2

(10089)
Illustration
Execution time
Operation
11.1 µs
The block controls the three analogue inputs (AI1...AI3) of a FIO-11 Analog I/O
Extension mounted on slot 2 of the drive control unit.
The block outputs both the unscaled (AIx) and scaled (AIx scaled) actual values of each
analogue input. The scaling is based on the relationship between the ranges
AIx min ... AIx max and AIx min scale ... AIx max scale.
AIx Min must be smaller than AIx Max; AIx Max Scale can be greater or smaller than AIx
Min Scale.
AIx Min Scale < AIx Max Scale
AIx scaled
32768
AIx Max Scale
-11 V or
-22 mA
AIx Min Scale
-32768
299
AIx [V or mA]
11 V or
22 mA
Standard function blocks