40.03 SLIP GAIN
Defines the slip gain which is used to improve the estimated motor slip. 100% means full slip gain; 0%
means no slip gain. The default value is 100%. Other values can be used if a static speed error is
detected despite of the full slip gain.
Example (with nominal load and nominal slip of 40 rpm): A 1000 rpm constant speed reference is
given to the drive. Despite of the full slip gain (= 100%), a manual tachometer measurement from the
motor axis gives a speed value of 998 rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To
compensate the error, the slip gain should be increased. At the 105% gain value, no static speed error
exists (2 rpm / 40 rpm = 5%).
0...200%
40.04 VOLTAGE RESERVE
Defines the minimum allowed voltage reserve. When the voltage reserve has decreased to the set
value, the drive enters the field weakening area.
If the intermediate circuit DC voltage U
maximum output voltage in steady-state operation is
0.95 × 550 V / sqrt(2) = 369 V
The dynamic performance of the motor control in the field weakening area can be improved by
increasing the voltage reserve value, but the drive enters the field weakening area earlier.
-4...50%
40.05 FLUX OPT
Enables the flux optimisation function. Flux optimisation improves motor efficiency and reduces noise.
Flux optimisation is used in drives that usually operate below nominal load.
Note: With a permanent magnet motor, flux optimisation is always enabled regardless of this
parameter.
(0) Disable
(1) Enable
40.06 FORCE OPEN LOOP
Defines the speed/position information used by the motor model.
(0) FALSE
(1) TRUE
FW block:
MOTOR CONTROL
Slip gain.
FW block:
MOTOR CONTROL
= 550 V and the voltage reserve is 5%, the RMS value of the
dc
Minimum allowed voltage reserve.
FW block:
MOTOR CONTROL
Flux optimisation disabled.
Flux optimisation enabled.
FW block:
MOTOR CONTROL
Motor model uses the speed feedback selected by parameter
SPEED FB
SEL.
Motor model uses the internal speed estimate (even when parameter
22.01 SPEED FB SEL
setting is
(see above)
(see above)
(see above)
(see above)
(1) Enc1 speed
/
(2) Enc2
Parameters and firmware blocks
157
22.01
speed).