ABB ACSM1 Firmware Manual page 177

Motion control drives, speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

51.30 MAPPING FILE VER
Displays the fieldbus adapter module mapping file revision stored in the memory of the drive.
In hexadecimal format. Example: 0x107 = revision 1.07.
51.31 D2FBA COMM STA
Displays the status of the fieldbus adapter module communication.
(0) IDLE
(1) EXEC. INIT
(2) TIME OUT
(3) CONFIG ERROR
(4) OFF-LINE
(5) ON-LINE
(6) RESET
51.32 FBA COMM SW VER
Displays the common program revision of the adapter module.
In format axyz, where a = major revision number, xy = minor revision numbers. z = correction letter.
Example: 190A = revision 1.90A.
51.33 FBA APPL SW VER
Displays the application program revision of the adapter module.
In format axyz, where: a = major revision number, xy = minor revision numbers, z = correction letter.
Example: 190A = revision 1.90A.
FW block: None
FW block: None
Adapter not configured.
Adapter initializing.
A timeout has occurred in the communication between the adapter
and the drive.
Adapter configuration error – the major or minor revision code of the
common program revision in the fieldbus adapter module is not the
revision required by the module (see par.
VER), or mapping file upload has failed more than three times.
Adapter is off-line.
Adapter is on-line.
Adapter is performing a hardware reset.
FW block: None
FW block: None
51.32 FBA COMM SW
Parameters and firmware blocks
177