Measuring the insulation resistance of the brake resistor circuit

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or
death, or damage to the equipment can occur. If you are not a qualified
electrical professional, do not do installation, commissioning or
maintenance work.
1.
Stop the drive and do the steps in section
precautions (page 16)
2. Make sure that the resistor cable is connected to the resistor and disconnected
from the drive output terminals.
3. At the drive end, connect the R+ and R- conductors of the resistor cable
together. Measure the insulation resistance between the conductors and the
PE conductor with a measuring voltage of 1000 V DC. The insulation resistance
must be more than 1 Mohm.

Grounding system compatibility check

EMC filter

The drive ACS180-04S-...-1/4 has an internal EMC filter as standard. You can install
a drive that has the internal EMC filter connected to a symmetrically grounded
TN-S system (center-grounded wye). For other systems, refer to
EMC filter with the grounding system (page
Note: If you disconnect the EMC filter, the electromagnetic compatibility of the
drive decreases.
before you start the work.
ohm
1000 V DC,
> 1 Mohm
Electrical installation 63
Electrical safety
R+
R-
PE
64).