Fba A Data In; Fba A Data Out - ABB ACS880 Series Firmware Manual

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

No.
Name/Value
51.33
FBA A appl SW ver
52

52 FBA A data in

52.01
FBA A data in1
None
CW 16bit
Ref1 16bit
Ref2 16bit
SW 16bit
Act1 16bit
Act2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
SW 32bit
Act1 32bit
Act2 32bit
SW2 16bit
Other
...
...
52.12
FBA A data in12
53

53 FBA A data out

53.01
FBA A data out1
None
CW 16bit
Ref1 16bit
Ref2 16bit
CW 32bit
Ref1 32bit
Ref2 32bit
CW2 16bit
Description
Displays the major and minor versions of the adapter module
firmware in format xyy, where x = major revision number, yy =
minor revision number.
Example: 300 = 3.00 (major version 3, minor version 00).
Major and minor versions of adapter module firmware.
Selection of data to be transferred from drive to fieldbus
controller through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
52.01...52.12
the drive to the fieldbus controller through fieldbus adapter A.
None.
Control Word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Status Word (16 bits)
Actual value ACT1 (16 bits)
Actual value ACT2 (16 bits)
Control Word (32 bits)
Reference REF1 (32 bits)
Reference REF2 (32 bits)
Status Word (32 bits)
Actual value ACT1 (32 bits)
Actual value ACT2 (32 bits)
Status Word 2 (16 bits)
Source selection (see
Terms and abbreviations
...
See parameter
52.01 FBA A data in1.
Selection of data to be transferred from fieldbus controller to
drive through fieldbus adapter A.
Note: 32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
53.01...53.12
the fieldbus controller to the drive through fieldbus adapter A.
None.
Control Word (16 bits)
Reference REF1 (16 bits)
Reference REF2 (16 bits)
Control Word (32 bits)
Reference REF1 (32 bits)
Reference REF2 (32 bits)
Control Word 2 (16 bits)
select data to be transferred from
on page 112). -
select data to be transferred from
Parameters 333
Def/FbEq16
-
None
0
1
2
3
4
5
6
11
12
13
14
15
16
24
...
None
None
0
1
2
3
11
12
13
21