378 Parameters
No.
Name/Value
91.22
Module 1 temp filter
time
0...10000 ms
91.24
Module 2 temp
sensor type
None
PTC
KTY-84
91.25
Module 2 temp filter
time
0...10000 ms
91.31
Module 1 TTL
output source
Not selected
Module input 1
Module input 2
91.32
Module 1 emulation
pulses/rev
0...65535
91.33
Module 1 emulated
Z-pulse offset
0.00000 ... 1.00000
rev
91.41
Module 2 TTL
output source
Not selected
Module input 1
Module input 2
91.42
Module 2 emulation
pulses/rev
0...65535
91.43
Module 2 emulated
Z-pulse offset
0.00000 ... 1.00000
rev
Description
Defines a filtering time for the temperature measurement
through interface module 1.
Filtering time for temperature measurement.
Specifies the type of temperature sensor connected to
interface module 2.
None.
PTC. (The unit is ohms.)
KTY84. (The unit is selected by parameter
selection.)
Defines a filtering time for the temperature measurement
through interface 2.
Filtering time for temperature measurement.
Selects the encoder input on interface module 1 whose signal
is echoed by or emulated to the TTL output.
See also section
Encoder support
TTL output not in use.
Input 1 is echoed by or emulated to the TTL output.
Input 2 is echoed by or emulated to the TTL output.
Defines the number of TTL pulses per revolution for encoder
emulation output of interface module 1.
Number of TTL pulses for emulation.
With interface module 1, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is emulated
whenever the encoder position passes zero position.
Position of emulated zero pulses.
Selects the encoder input on interface module 2 whose signal
is echoed by or emulated to the TTL output.
See also section
Encoder support
TTL output not in use.
Input 1 is echoed by or emulated to the TTL output.
Input 2 is echoed by or emulated to the TTL output.
Defines the number of TTL pulses per revolution for encoder
emulation output of interface module 2.
Number of TTL pulses for emulation.
With interface module 2, defines when zero pulses are
emulated in relation to zero position received from the
encoder.
For example, with a value of 0.50000, a zero pulse is
emulated whenever the encoder position passes 0.5
revolutions. With a value of 0.00000, a zero pulse is emulated
whenever the encoder position passes zero position.
Position of emulated zero pulses.
96.16 Unit
(page 51).
(page 51).
Def/FbEq16
1500 ms
-
None
0
1
2
1500 ms
-
Not selected
0
1
2
0
1 = 1
0.00000
32767 =
1 rev
Not selected
0
1
2
0
1 = 1
0
32767 =
1 rev