ABB ACS880 Series Firmware Manual page 400

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

400 Parameters
No.
Name/Value
96.54
Checksum action
No action
Pure event
Warning
Warning and
prevent start
Fault
96.55
Checksum control
word
Bit
Name
0
Approved checksum 1
1
Approved checksum 1
2
Approved checksum 1
3
Approved checksum 1
4
Set approved checksum 1 1 = Set: Copy value of
5
Set approved checksum 1 1 = Set: Copy value of
6
Set approved checksum 1 1 = Set: Copy value of
7
Set approved checksum 1 1 = Set: Copy value of
8...15
Reserved
00000000b...
11111111b
96.56
Approved
checksum 1
00000000h...
FFFFFFFFh
96.57
Approved
checksum 2
00000000h...
FFFFFFFFh
96.58
Approved
checksum 3
00000000h...
FFFFFFFFh
96.59
Approved
checksum 4
00000000h...
FFFFFFFFh
Description
Selects how the drive reacts if the parameter checksum
(96.53 Actual
checksum) does not match any of the active
approved checksums (96.56...96.59). The active checksums
are selected by
96.55 Checksum control
No action taken. (The checksum feature is not in use.)
The drive generates an event log entry
mismatch).
The drive generates a warning
The drive generates a warning
Starting the drive is prevented.
The drive trips on
6200 Checksum
Bits 0...3 select to which approved checksums (out of
96.56...96.59) the actual checksum (96.53) is compared.
Bits 4...7 select an approved (reference) checksum
parameter (96.56...96.59) into which the actual checksum
from parameter
96.53
is copied.
Description
1 = Enabled: Checksum 1 (96.56) is observed.
1 = Enabled: Checksum 2 (96.57) is observed.
1 = Enabled: Checksum 3 (96.58) is observed.
1 = Enabled: Checksum 4 (96.59) is observed.
Checksum control word.
Approved (reference) checksum 1.
Approved checksum 1.
Approved (reference) checksum 2.
Approved checksum 2.
Approved (reference) checksum 3.
Approved checksum 3.
Approved (reference) checksum 4.
Approved checksum 4.
word.
(B686 Checksum
(A686 Checksum
mismatch).
(A686 Checksum
mismatch).
mismatch.
96.53
into
96.56.
96.53
into
96.57.
96.53
into
96.58.
96.53
into
96.59.
Def/FbEq16
No action
0
1
2
3
4
00000000b
1 = 1
0h
-
0h
-
0h
-
0h
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-01Acs880-37Acs880-04Acs880-07Acs880-17