No.
Name/Value
05.42
Aux. fan service
counter
0...150%
06
06 Control and status
words
06.01
Main control word
0000h...FFFFh
06.02
Application control
word
0000h...FFFFh
06.03
FBA A transparent
control word
00000000h ...
FFFFFFFFh
06.04
FBA B transparent
control word
00000000h ...
FFFFFFFFh
06.05
EFB transparent
control word
00000000h ...
FFFFFFFFh
Description
Displays the age of the auxiliary cooling fan as a percentage
of its estimated lifetime. The estimate is based on the duty,
operating conditions and other operating parameters of the
fan. When the counter reaches 100%, a warning
service
counter) is generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Auxiliary cooling fan age.
Drive control and status words.
The main control word of the drive. This parameter shows the
control signals as received from the selected sources (such
as digital inputs, the fieldbus interfaces and the application
program).
The bit assignments of the word are as described on page
539. The related status word and state diagram are presented
on pages
540
and
541
respectively.
Note: Bits 12...15 can be used to carry additional control
data, and used as a signal source by any binary-source
selector parameter.
This parameter is read-only.
Main control word.
The drive control word received from the application program
(if any). The bit assignments are described on page 539.
This parameter is read-only.
Application program control word.
Displays the unaltered control word received from the PLC
through fieldbus adapter A when a transparent
communication profile is selected eg. by parameter group
FBA A
settings. See section
(page 536).
This parameter is read-only.
Control word received through fieldbus adapter A.
Displays the unaltered control word received from the PLC
through fieldbus adapter B when a transparent
communication profile is selected eg. by parameter group
FBA B
settings. See section
(page 536).
This parameter is read-only.
Control word received through fieldbus adapter B.
Displays the unaltered control word received from the PLC
through the embedded fieldbus interface when a transparent
communication profile is selected in parameter
profile. See section
The Transparent profile
This parameter is read-only.
Control word received through the embedded fieldbus
interface.
(A8C0 Fan
Control word and Status word
Control word and Status word
58.25 Control
(page 526).
Parameters 127
Def/FbEq16
-
1 = 1%
-
1 = 1
-
1 = 1
-
51
-
-
54
1 = 1
-
1 = 1