ABB ACS880 Series Firmware Manual page 506

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

506 Fault tracing
Code
Fault
(hex)
FB11
Memory unit missing
FB12
Memory unit
incompatible
FB13
Memory unit FW
incompatible
FB14
Memory unit FW load
failed
FF61
ID run
0005...0008 Internal error.
Cause
No memory unit is attached to
the control unit.
The memory unit attached to
the control unit is empty.
The memory unit attached to
the control unit is incompatible.
The firmware on the attached
memory unit is incompatible
with the drive.
The firmware on the attached
memory unit could not be
loaded to the drive.
Motor ID run was not
completed successfully.
0001 Maximum current limit too low.
0002 Maximum speed limit or
calculated field weakening
point too low.
0003 Maximum torque limit too low.
0004 Current measurement
calibration did not finish within
reasonable time.
What to do
Power down the control unit.
Check that the memory unit is properly
inserted into the control unit.
Power down the control unit. Attach a
memory unit (with the appropriate
firmware) to the control unit.
Power down the control unit.
Attach a compatible memory unit.
Power down the control unit.
Attach a memory unit with compatible
firmware.
Power down the control unit.
Check that the memory unit is properly
inserted into the control unit.
If the problem persists, replace the
memory unit.
Check the nominal motor values in
parameter group
99 Motor
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that the motor shaft is not locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
Check settings of parameters
Motor nominal current
and
Maximum
current. Make sure that
30.17
> 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Check settings of parameters
30.11 Minimum speed
30.12 Maximum speed
99.07 Motor nominal voltage
99.08 Motor nominal frequency
99.09 Motor nominal
Make sure that
30.12
> (0.55 × 99.09) >
(0.50 × synchronous speed)
30.11
< 0, and
• supply voltage > (0.66 × 99.07).
Check settings of parameter
nominal
torque, and the torque limits in
group
30
Limits.
Make sure that the maximum torque limit
in force is greater than 100%.
Contact your local ABB representative.
Contact your local ABB representative.
data.
99.06
30.17
speed.
99.12 Motor