ABB ACS880 Series Firmware Manual page 158

Industrial drives, primary control program
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

158 Parameters
No.
Name/Value
13.17
AO1 source min
-32768.0 ...
32767.0
13.18
AO1 source max
-32768.0 ...
32767.0
13.19
AO1 out at AO1 src
min
0.000 ... 22.000 mA Minimum AO1 output value.
13.20
AO1 out at AO1 src
max
0.000 ... 22.000 mA Maximum AO1 output value.
Description
Defines the real minimum value of the signal (selected by
parameter
13.12 AO1
source) that corresponds to the
minimum required AO1 output value (defined by parameter
13.19 AO1 out at AO1 src
I
(mA)
AO1
13.20
13.19
13.17
Programming
13.17
as the maximum value and
minimum value inverts the output.
I
(mA)
AO1
13.20
13.19
13.18
Real signal value corresponding to minimum AO1 output
value.
Defines the real maximum value of the signal (selected by
parameter
13.12 AO1
source) that corresponds to the
maximum required AO1 output value (defined by parameter
13.20 AO1 out at AO1 src
source
min.
Real signal value corresponding to maximum AO1 output
value.
Defines the minimum output value for analog output AO1.
See also drawing at parameter
Defines the maximum output value for analog output AO1.
See also drawing at parameter
min).
13.18
Signal (real)
selected by
13.12
13.18
13.17
Signal (real)
selected by
13.12
max). See parameter
13.17 AO1
13.17 AO1 source
13.17 AO1 source
Def/FbEq16
0.0
as the
1 = 1
1500.0;
1800.0
(95.20
b0)
1 = 1
0.000 mA
min.
1000 = 1 mA
20.000 mA
min.
1000 = 1 mA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: