490 Fault tracing

Fault messages

Code
Fault
(hex)
2281
Calibration
2310
Overcurrent
2330
Earth leakage
Programmable fault:
Earth fault
Cause
Measured offset of output
phase current measurement or
difference between output
phase U2 and W2 current
measurement is too great (the
values are updated during
current calibration).
Output current has exceeded
internal fault limit.
Drive has detected load
unbalance typically due to
31.20
earth fault in motor or motor
cable.
What to do
Try performing the current calibration
again (select
Current measurement
calibration
at parameter 99.13). If the
fault persists, contact your local ABB
representative.
Check motor load.
Check acceleration times in parameter
group
23 Speed reference ramp
control),
26 Torque reference chain
(torque control) or
28 Frequency
reference chain
(frequency control). Also
check parameters
31.42 Overcurrent
fault
limit,
46.01 Speed
Frequency scaling
and
46.03 Torque
scaling.
Check motor and motor cable (including
phasing and delta/star connection).
Check there are no contactors opening
and closing in motor cable.
Check that the start-up data in parameter
group 99 corresponds to the motor rating
plate.
Check that there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check encoder cable (including
phasing).
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected inverter
modules, "Y YY" specifies through which
BCU control unit channel the fault was
received. "ZZ" indicates the phase that
triggered the fault (0: No detailed
information available, 1: U-phase, 2: V-
phase, 4: W-phase, 3/5/6/7: multiple
phases).
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
Motor control
mode.)
With parallel-connected modules, check
the auxiliary code (format XXXY YYZZ).
"Y YY" specifies through which BCU
control unit channel the fault was
received.
If no earth fault can be detected, contact
your local ABB representative.
(speed
scaling,
46.02
99.04