No.
Name/Value
31.38
Ramp stop
supervision delay
0...32767 s
31.40
Disable warnings
Bit
Fault
0
Overvoltage
1
Reserved
2
Encoder 1
3
Encoder 2
4...15
Reserved
0000b...1101b
31.42
Overcurrent fault
limit
0.0 ... 30000.0 A
32

32 Supervision

32.01
Supervision status
Bit
Name
0
Supervision 1 active
1
Supervision 2 active
2
Supervision 3 active
3...15
Reserved
0000...0111b
Description
If parameter
31.37 Ramp stop supervision
parameter defines the maximum time a ramp stop is allowed
to take. If the motor has not stopped when the time elapses,
the drive trips on
73B1 Stop
status word
2, and coasts to a stop.
If
31.37
is set to a value other than 0%, this parameter
defines a delay between the receipt of the stop command and
the activation of the supervision. It is recommended to specify
a short delay to allow the speed change rate to stabilize.
Maximum ramp-down time, or supervision activation delay.
Selects warnings to be suppressed. The parameter is a 16-bit
word with each bit corresponding to a warning. Whenever a
bit is set to 1, the corresponding warning is suppressed.
The bits of this binary number correspond to the following
warnings:
Warning suppression word.
Sets a custom motor current fault limit.
The drive automatically sets an internal motor current limit
according to the drive hardware. The internal limit is
appropriate in most cases, but this parameter can be used to
set a lower current limit, for example, to protect a permanent
magnet motor from demagnetization.
With this parameter at 0.0 A, only the internal limit is in force.
Custom motor current fault limit.
Configuration of signal supervision functions 1...3.
Three values can be chosen to be monitored; a warning or
fault is generated whenever predefined limits are exceeded.
See also section
Signal supervision
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note: This word is independent of the drive actions defined
by parameters 32.06,
32.16
Description
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
Signal supervision status word.
is set to 0%, this
failed, sets bit 14 of
06.17 Drive
(page 87).
and 32.26.
32.07
is outside its limits.
32.17
is outside its limits.
32.27
is outside its limits.
Parameters 263
Def/FbEq16
0 s
1 = 1 s
0000b
1 = 1
-
See par.
46.05
0000b
1 = 1