376 Parameters
No.
Name/Value
91
91 Encoder module
settings
91.01
FEN DI status
Bit
Name
0
DI1 /module 1
1
DI2 /module 1
2...3
Reserved
4
DI1 /module 2
5
DI2 /module 2
6...15
Reserved
0000 0000b ...
0011 0011b
91.02
Module 1 status
No option
No communication
Unknown
FEN-01
FEN-11
FEN-21
FEN-31
FSE-31
91.03
Module 2 status
91.04
Module 1
temperature
0...1000 °C, °F or
ohm
91.06
Module 2
temperature
0...1000 °C, °F or
ohm
Description
Configuration of encoder interface modules.
Displays the status of the digital inputs of FEN-xx encoder
interface modules.
This parameter is read-only.
Information
DI1 of interface module 1 (see parameters
DI2 of interface module 1 (see parameters
DI1 of interface module 2 (see parameters
DI2 of interface module 2 (see parameters
Status word of digital inputs on FEN-xx modules.
Displays the type of the interface module found in the location
specified by parameter
91.12 Module 1
This parameter is read-only.
No module detected in the specified slot.
A module has been detected but cannot be communicated
with.
The module type is unknown.
An FEN-01 module has been detected and is active.
An FEN-11 module has been detected and is active.
An FEN-21 module has been detected and is active.
An FEN-31 module has been detected and is active.
An FSE-31 module has been detected and is active.
Displays the type of the interface module found in the location
specified by parameter
91.14 Module 2
For the indications, see parameter
This parameter is read-only.
Displays the temperature measured through the sensor input
of interface module 1. The unit is selected by parameter
96.16 Unit
selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Temperature measured through interface module 1.
Displays the temperature measured through the sensor input
of interface module 2. The unit is selected by parameter
96.16 Unit
selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
Temperature measured through interface module 2.
91.11
and 91.12)
91.11
and 91.12)
91.13
and 91.14)
91.13
and 91.14)
location.
location.
91.02 Module 1
status.
Def/FbEq16
-
1 = 1
-
0
1
2
16
17
18
21
25
-
-
-
-
-